Okay, it's starting.
2
Okay, it's our recording now.
3
Umar, please go ahead to start and first please introduce yourself and then go ahead to start the presentation.
4
So, thank you for joining us today.
5
My name is Muhammad Umar Afzal and I'm a PhD student at the University of Tennessee Knoxville.
6
My advisor is Dr. Ye Lu Lu.
7
Today I will talk about the identification
8
and mitigation of subsynchronous oscillation using the real 20 hertz event in the Kwai Island power system.
9
I will show how we created oscillatory behavior in an EMT model,
10
how inverter control settings affected the response and how we develop a point of wave method to detect these oscillations.
11
Here's a quick overview of what I will cover today.
12
I will begin with the 20 hertz event observed in Kauai.
13
Then I will introduce our PSCAD model and explain how we studied the sensitivity of the inverter controls.
14
After that I will show what the oscillations look like in the voltage waveform including the sideband frequencies
15
and discuss the mitigation techniques we identified.
16
At the end, I will discuss the point -of -wave sub -synchronous oscillation detection approach.
17
Let me start why these oscillations are getting more attention.
18
Traditionally, a large portion of electricity was generated by a synchronous generator.
19
Their rotating masses provide physical inertia, and they can also supply substantial fault current during a disturbance.
20
Today, we are integrating more solar, wind, and battery energy storage system through power electronic converters.
21
The chart on the left shows how much these technologies have grown.
22
As the generation mix changes, the way the power system responds to disturbance also changes.
23
On the right, a simple comparison between synchronous generators and IBRs.
24
One important difference is inertia.
25
Synchronous machines store kinetic energy in their rotating masses.
26
Inverters don't inherently provide the same physical response.
27
A second difference is fault current ibr generally have limited fault current contributions
28
and conventional synchronous machine and the third one is the control behavior
29
and inverter response depends on its busy phase lock loop current
30
and voltage controllers power controllers and filters these control loops interact with the electrical network
31
and under certain operating conditions these interactions can produce oscillations on
32
november 2021 at around 5 30 in the morning an oil -fired power plant trip in the Kwai Island power system.
33
Following that disturbance, an oscillation around 18 to 20 Hz was observed and the oscillation sustained for roughly a minute.
34
These kind of oscillations matter because they can stress equipment, affect control performance, and potentially cause additional trips if their magnitude is large enough.
35
Our task at that time was to recreate that 20 Hz oscillation
36
and then investigate which control settings are responsible for that 20 hertz oscillations.
37
Now to recreate the 20 hertz oscillation event,
38
we first need to develop a detailed model of the Kwai Island power system in a suitable simulation environment.
39
The NREL NLR now research team was also involved in this work with us.
40
They had investigated before me when I started work on it, they had investigated this event and found
41
that the phasor domain models in PSSC were not able to reproduce this 20 hertz oscillation event.
42
So we decided to use an electromagnetic transient simulation environment and we developed the Kwai Island power system model in PSCAS.
43
Most of the system parameters and operating conditions were obtained from KIUC.
44
For the parameters where detailed information was not available, we used the default model settings.
45
Now, if you look at the diagram on the right, it shows the simplified Kauai island power system.
46
The system contains three synchronous generators
47
and four IBRs with approximately 40 megawatts of load connected through our 57 .1 kV transmission network.
48
For modeling the synchronous power plant, we use the detailed dynamic models available in the PSCAD library,
49
including synchronous generator, turbines, governor, excitation system, and power system stabilizers.
50
For the IBRs, we use detail model developed by Dr. Deepak's team from APRI.
51
At that time, APRI had recently developed these IBR models and made them openly available for research.
52
The inverter model is quite detailed and includes both grid following and grid forming modes.
53
So we ran the system and system is operating perfectly in steady state conditions.
54
So the next task was which control parameters are responsible for the 20 hertz oscillation.
55
So we have to trip a generator, one synchronous generator with the same amount
56
and have to see like how we can produce the 20 hertz oscillation in the system.
57
for this ibr models contain many control parameters we have pll gains current control gains voltage control gains active
58
and reactive power control gains and filter changing all of these manually
59
and running separate simulation would take a lot of time
60
so we develop an automated sensitivity analyzer in pscat at
61
that time this sensitivity analyzer this was in 2020 2023
62
and it was like I think it was like old approach
63
now today I have developed an AI copilot for PSCAD where I simply type a command into the chat box
64
and PSCAD automatically take care of everything but at
65
that time we don't have these AI copilot I have not access to these LLM models
66
and stuff but anyhow this sensitivity analyzer idea is very straightforward we select a control parameter
67
and define the range of values we want to set.
68
The analyzer changed that parameter while keeping the other settings fixed and store the results.
69
It was just basically an automation process.
70
Instead of waiting for each simulation to finish and manually start the next one and then collecting the result, it could run series of simulation automatically.
71
The results were stored automatically
72
and afterward I could analyze them using FFT to identify the oscillation frequency related to
73
which parameter settings the oscillation is related to
74
and what behavior look like once one parameter has been tested the analyzer moved to the next parameter
75
and then it stored the results of another parameters automatically
76
several control gains affected the response of frequency but we find out
77
that the pll proportional gain showed a strong relationship with the subsynchronous oscillation
78
so here you can see so when we find out
79
that the pll proportional gain is generating some type of the oscillation
80
which is related to actual koi island event
81
so then we modified the sensitivity analyzer
82
and start focusing more on this pll parameter
83
so here this is the slide which i'm showing here this is one of the main results of our sensitivity analysis.
84
A PLL proportional gain of 12 .5
85
and an integral gain of 100 together with the shunt compensation
86
in the network produce an oscillation at 20 hertz in our model.
87
The graph shows the FFT of the frequency signal.
88
This is the clear peak at 20 hertz, which identifies the dominant oscillatory component in this case.
89
On the right, the table lists the controller parameter used in this simulation.
90
These mostly controller parameters are the default parameters available in the APRI model,
91
and the only change here which is not the default is this PLL proportional gain.
92
After creating the 20 Hz oscillation, we used the analyzer to see how the response changed as we changed the PLL proportional gain.
93
And then we did more sensitivity analysis on the PLL proportional gain.
94
We swept the PLL proportional gain from about 5, from here, from about 5 to 55 during a 200 -second simulation,
95
increasing it by 0 .5 every 2 seconds while keeping other parameters fixed.
96
Here, the horizontal axis is simulation time and the vertical axis is the PLL proportional gain.
97
The blue line shows the gradual increase in gain and the colored points mark the oscillation frequencies we observed at different settings.
98
For example, at gain of 12 .5, the oscillation was approximately 20 Hz.
99
At gain of 17, it was around 22 Hz.
100
And when the gain reached 30, the oscillation was close to 25 Hz.
101
The table on the right summarizes these results.
102
The plot shows the short time Fourier transform
103
you can see the dominant oscillatory band moving upward from approximately 17 to 20 hertz as the gain increases.
104
Another important observation in this analysis is
105
that the oscillation eventually became damp like here in this area as we continue to increase the PLL gain.
106
So this is the one of our mitigation strategy as well.
107
A separate simulation with the proportional gain set to 40, PLL proportional gain, showed a stable response following the generation trip.
108
So the PLL proportional gain higher than the 40 will result in no oscillation.
109
So far, we have looked at the oscillation in the phasor domain.
110
Now I will just show a quick look at how it looks like in point -of -wave data.
111
The graph shows the phase voltage from the EMT simulation.
112
On the right side is the FFT spectrum of that waveform.
113
The main peak is the 60 Hz fundamental, but you can see two additional peaks, one at 40 Hz and another at 80 Hz.
114
These are sidebands around the fundamentals.
115
So in point of wave data, the 20 Hz oscillation will appear as the 40 and 80 Hz sideband.
116
now that we have identified the control
117
and network condition associated with the oscillation the next part is how can mitigate it
118
and the first thing is the PLL tuning and we already identify
119
if we increase the proportional gain to 40 it will damp the oscillation
120
we keep trying finding some other damping techniques
121
and we also use the sensitivity analyzer for that and the The second was that if we strengthen the voltage control response,
122
increasing the voltage control proportional gain from 0 .5 to 1, improved damping in our simulation.
123
We also examined the share of synchronous generation remaining after the trip.
124
In the system, maintaining about 35 % of total generation from synchronous plots after tripping will result in no oscillation of the system.
125
So this is related to strong grid or grid strength,
126
high grid strength related as well.
127
So the another thing we just changed the IBR mode, we change it from grid forming to grid forming.
128
So then there is no oscillation.
129
And the fifth one is also very important, like there is a shunt compensation in the system.
130
And when I remove the shunt compensation, then there is also no oscillation in the system
131
so i think it is related to
132
because the event happened in the early morning
133
and there is less industrial load on the system
134
or less reactive load so there might be chances that the shunt compensation is playing role in the oscillation as well
135
moving on we went towards the detection approach like how to
136
detect these sub -synchronous oscillation as everyone know nowadays point of wave data is getting
137
so much importance because it contains so much hidden information
138
which phasor data is not able to reveal so for the sub -synchronous oscillation detector part, we started with a simple technique.
139
In steady 60 hertz system, one waveform cycle should look very similar to the next.
140
When an oscillation develops, the amplitude and shape can begin to change from one cycle to another cycle.
141
And here you can see
142
that the plot here shows a normalized current waveform whose envelope changes our time below
143
it the FFT shows the same 40 and 80 Hertz sideband pattern we discussed earlier
144
now
145
if you look at the waveform on the right the red box represent one complete cycle of the current waveform
146
we compare each sample of the current cycle with the corresponding sample of the previous cycle
147
then we can play the difference between the two cycle and compare it with the predefined threshold.
148
If the difference exceeds that threshold, the algorithm detects an oscillation in the system.
149
So the basic idea is to identify oscillation by monitoring how the waveform change from one cycle to the other.
150
The main advantage of this approach is that it is very simple.
151
However, one major limitation is that it cannot reliably detect slowly growing oscillations.
152
When an oscillation develops gradually, the difference between two consecutive cycles can be very small as
153
as a result the difference may not exceed the detection threshold to evaluate the performance of this algorithm
154
we tested it continuously throughout the simulation time
155
following the generation trip
156
if you look at the pie chart on the left the
157
detection rate was only about 39 percent to improve the method
158
we changed the reference cycle instead of comparing every cycle with its immediate neighbor we use one fixed healthy reference cycle
159
so in this slide on the right the yellow box marks the reference cycle
160
which stays the same throughout the comparison the red box marks a letter cycle
161
that we are evaluating rather than asking how different two neighboring
162
cycles are we now ask how different the incoming cycle is from our original reference
163
that makes it easier to detect a change
164
that developed gradually the results were better
165
and accuracy increased up to 66 .86 percent
166
when oscillations are present the point of wave data shows a varying amplitude envelope
167
so some cycles can look almost identical to the reference cycle like here you can see
168
when there is some envelope and when envelope is going down
169
so some of cycles will become in the range of this healthy cycle
170
so this approach will not able to detect that cycle so
171
so that's how the algorithm accuracy is 16 66 .86 percent to overcome this limitation we introduce a window based comparison method
172
So, instead of making our detection decision based on a single cycle, we compare multiple cycles over a window.
173
We use our window consists of three cycles.
174
For each cycle, we compare each sample with the corresponding sample of the reference cycle.
175
We calculate the absolute difference and take their average
176
if the average deviation is above the threshold the algorithm flags and oscillation as the
177
here you can see in the pie chart the algorithm detection rate increases up to 98 percent
178
so yeah I think yeah I think it's I completed my slides very quickly so here is our ongoing work.
179
So as we already have the EMT test bench of Kauai Island and a method to reproduce the oscillation,
180
we started finding some unique oscillation source localization feature.
181
We already have identified some feature that could help us to locate the oscillation source without requiring information about the network topology.
182
And we are also developing an integrated tool that can automatically detect these oscillation and identify their source.
183
But this work is still in process and I can share these work later.
184
And these are all research papers related to this high -level overview talk
185
which I just uh finish now so yes i think it's a quick task
186
so we can discuss some questions and answers now

App downloaden

Alles wat je nodig hebt om vloeiend te spreken

AI UitspraakScoor elke zin
IPA OefeningBeheers elk geluid
WoordenschatBouw je woordenschat op
WoordenspelLeren terwijl je speelt
FOR YOU

Aanbevolen Video

Woordenschat en spreektips bij deze les

Deze spreekles is gebaseerd op de video “Identification and Mitigation of Subsynchronous Oscillations”. Deze woorden komen het vaakst terug: oscillation, cycle, gain, parameter, pll. Deze video bevat 186 zinnen en 2438 woorden om na te spreken. Het gesproken deel duurt 18:12. De spreker praat in een gelijkmatig tempo van ongeveer 134 woorden per minuut, prettig om te shadowen. Slechts 77% van de woorden hoort bij de 3.000 meest gebruikte Engelse woorden, dus de woordenschat is pittig.

Belangrijke woorden in deze video

15 woorden uit de video die het leren waard zijn, met uitspraak en betekenis:

WoordUitspraakBetekenis
proportional bijvoeglijk naamwoordevenredig
sensitivity zelfstandig naamwoord/ˌsɛn.səˈtɪv.ə.ti/gevoeligheid
grid zelfstandig naamwoord/ɡɹɪd/raster
detect werkwoord/dɪˈtɛkt/detecteren
voltage zelfstandig naamwoord/ˈvəʊltɪd͡ʒ/spanning
generator zelfstandig naamwoord/ˈdʒɛnəɹeɪtə(ɹ)/generator
compare werkwoord/kəmˈpɛɚ/vergelijken
frequency zelfstandig naamwoord/ˈfɹiːkwənsi/frequentie
algorithm zelfstandig naamwoord/ˈælɡəɹɪðm̩/algoritme
compensation zelfstandig naamwoord/ˌkɑm.pənˈseɪ.ʃən/compensatie
threshold zelfstandig naamwoord/ˈθɹɛʃ(h)oʊld/drempel
envelope zelfstandig naamwoord/ˈɛnvə(ˌ)loʊp/envelop, briefomslag
damp bijvoeglijk naamwoord/ˈdæmp/klam
introduce werkwoord/ˌɪntɹəˈdus/introduceren, voorstellen
investigate werkwoord/ɪnˈvɛs.tə.ɡeɪt/onderzoeken, bekijken

Phrasal verbs die je zult horen

WoordBetekenis
find out werkwoordontdekken, onderzoeken
go down werkwoordafdalen

Grammatica in deze video

De structuren die de spreker het meest gebruikt, met de exacte woorden uit de video:

StructuurIn de video
Present perfect have/has + voltooid deelwoord — iets uit het verleden dat nu nog telthave grown · have developed · has been tested
Lijdende vorm be + voltooid deelwoord — het gaat om wat er gebeurt, niet om wie het doetwas generated · was observed · was also involved

Uitspraak om op te letten

De spreker gebruikt 4 samentrekkingen en verkorte vormen, zoals don't, I'm. Spreek ze kort uit, zoals je ze hoort.

  • De “th”-klanken: algorithm /ˈælɡəɹɪðm̩/, threshold /ˈθɹɛʃ(h)oʊld/, strengthen /ˈstɹɛŋ(k)θən/
  • De klanken “sh” en “zh”: simulation /ˌsɪm.jəˈleɪ.ʃn̩/, detection /dɪˈtɛk.ʃən/, compensation /ˌkɑm.pənˈseɪ.ʃən/, threshold /ˈθɹɛʃ(h)oʊld/, limitation /lɪmɪˈteɪʃən/
  • Lange woorden — let op de klemtoon: parameter /pəˈɹæm.ə.tɚ/, sensitivity /ˌsɛn.səˈtɪv.ə.ti/, generator /ˈdʒɛnəɹeɪtə(ɹ)/, compensation /ˌkɑm.pənˈseɪ.ʃən/, investigate /ɪnˈvɛs.tə.ɡeɪt/

Klanken die Nederlandstaligen lastig vinden:

  • Stemhebbende eindmedeklinker — /b/, /d/, /g/, /z/, /v/ niet verscherpen: grid /ɡɹɪd/, voltage /ˈvəʊltɪd͡ʒ/, threshold /ˈθɹɛʃ(h)oʊld/, slide /ˈslaɪ̯d/, observe /əbˈzɜːv/
  • /æ/ — opener dan de Nederlandse “e”: parameter /pəˈɹæm.ə.tɚ/, algorithm /ˈælɡəɹɪðm̩/, damp /ˈdæmp/, accuracy /ˈæk.jɚ.ə.si/, gradually /ˈɡɹæd͡ʒuəli/
  • /g/ — een harde plofklank, geen Nederlandse “g”: grid /ɡɹɪd/, algorithm /ˈælɡəɹɪðm̩/, investigate /ɪnˈvɛs.tə.ɡeɪt/, gradually /ˈɡɹæd͡ʒuəli/, graph /ɡɹæf/

Zo oefen je met deze video

  1. Luister de hele video één keer zonder te spreken en noteer de woorden die je niet kent.
  2. Spreek zin voor zin na op normale snelheid en herhaal elke zin tot je ritme gelijk is aan dat van de spreker.
  3. Neem jezelf op en vergelijk met het origineel; let daarbij op woorden als proportional, sensitivity, grid.

Wat is de Shadowing-techniek?

Shadowing is een wetenschappelijk onderbouwde taalleermethode die oorspronkelijk is ontwikkeld voor professionele tolkentraining en gepopulariseerd door polyglot Dr. Alexander Arguelles. De methode is eenvoudig maar krachtig: je luistert naar native Engelse audio en herhaalt het onmiddellijk hardop — als een schaduw die de spreker volgt met slechts 1–2 seconden vertraging. In tegenstelling tot passief luisteren of grammaticadrills, dwingt shadowing je hersenen en mondspieren om echte spraakpatronen tegelijkertijd te verwerken en te reproduceren. Onderzoek toont aan dat het de uitspraaknauwkeurigheid, intonatie, ritme, verbonden spraak, luisterbegrip en spreekvaardigheid aanzienlijk verbetert — waardoor het een van de meest effectieve methoden is voor IELTS Speaking-voorbereiding en echte Engelse communicatie.

Shadowing-techniek: lees de volledige stap-voor-stap-gids →