All righty folks, Phil Zito here and welcome to day six of the BAS Bootcamp.
2
So what we're going to be looking at in today's video
3
is we're going to talk about the internal setup of inputs and outputs.
4
And then in tomorrow's video, we're going to start to look at the external setup of inputs and outputs.
5
So I mentioned in earlier videos of this BAS Bootcamp series
6
that you will often go and have these things called universal inputs.
7
And these universal inputs will allow you to go about setting your inputs
8
and outputs to do whatever they are capable of processing.
9
So let's take a look at what that might look like.
10
So I'm going to add a hardware input and I'm going to add a hardware output.
11
So right now I'm using DysTech GFX software, and we're going to take a look at setting up one of their inputs.
12
So we would go to the input, and we would see that right here, and this is how they set it up, and different software is going to look a little different.
13
But how they set it up is you'll have the name of the hardware input, and then it'll show signal disconnected disconnected.
14
Now this is a universal input so it's going to give me multiple different types of inputs I can process.
15
When we're looking at inputs we're really focused on those four input types that I talked about right?
16
The digital input also known as dry contact, the resistive input these are typically used for temperature,
17
or the linear input which is what we're typically going to use
18
if we're doing some form of voltage either volts DC or milliamps of current.
19
Let's take a look first at digital input because it's definitely the easiest.
20
So oftentimes when you're setting up a digital input the things you need to know are just just a handful of things.
21
First off you typically will have some form of action or polarity it'll be called something to to that effect.
22
And you need to pick, basically what you're saying is, is when this input is electrically, I was gonna say electronically,
23
but when it's electrically true, meaning it is actually true,
24
it's actually got the contacts are closed or it's energized, whatever is causing this digital input to be true,
25
when that's true in the program, it's going to represent a true or a one or some sort of true Boolean value.
26
If you don't want that to be the case, which is in some cases like when you're doing safeties
27
and you've got them wired to a specific output or a specific contact type.
28
Maybe you're using normally closed contacts, and you want those contacts to break to indicate failure.
29
Then you would actually click this reverse action and or the polarity button,
30
whatever your software has, and that would go and cause it to turn true when the input was actually false.
31
Also, on some controllers, you can go and set up their enumeration sets basically it's their data typesets.
32
All right, so let's then look at a different type of signal.
33
Let's look at RTDs.
34
Now, when it comes to RTDs and thermistors, you actually have these things called resistance tables.
35
So let me see if I can pull up one while I'm talking.
36
10k type 2 table.
37
okay and what this will look like i don't know how well this is gonna show up
38
but uh we'll see so basically what we can see right here is
39
that for certain degrees fahrenheit there are certain ohm resistance
40
because remember resistance is measured in ohms we learned
41
that in yesterday's video or last week's video rather day five
42
so we see that there's this chart and what happens inside the controller
43
when you pick the thermistor type like platinum 1000 ohm nickel 1000 ohm 10k type 2
44
what happens is there's actually a chart that this controller knows
45
and based on the resistance
46
that is sensed it is going to calculate temperature now what
47
you can do is a couple different things Not every controls line has this,
48
but typically they will have an offset for temperature.
49
You see this is delta degrees Fahrenheit because we're in degrees Fahrenheit.
50
So what would happen is as the test and balance went through
51
and they tested the sensors and they gave you the sensed value versus what you're seeing, you would actually put in a correction factor.
52
Sometimes you can also put in ohm correction factors.
53
I do not recommend doing this because that totally screws up your table.
54
I typically recommend just putting in an output offset.
55
So setting the actual offset right here for the actual sensed value.
56
All right.
57
So that's RTDs and thermistors.
58
Pretty straightforward also.
59
So, so far we've covered digital and we've covered RTD and thermistor.
60
Now, linear is something I see a lot of folks get really tripped up on.
61
They do have a resistance because sometimes you will be using a potentiometer to go and calculate a specific output,
62
but we're not going to go through that because that's less common.
63
What we're going to talk about really is 0 to 10 volts and 0 to 20 milliamps.
64
So 0 to 10 volts right here is we've got 0 to 10, and then our output is 0 to 100.
65
Now, this could be for a humidity sensor, in which case it would be 0 to 100.
66
This could be for a pressure sensor in
67
which it may be like 0 to 5 or 0 to 20 pounds per square.
68
It could be a variety of things that you're sensing.
69
And the important thing here to know when you're dealing with linear is what are my min and max signals?
70
So 0 to 10 or maybe it's 2 to 10, whatever it is.
71
and then what does that correspond to from an output perspective?
72
And it'll do all the calculations itself.
73
The same for the actual 4 to 20 milliamps, or 0 to 20 milliamps.
74
So if we wanted to do 4 to 20 milliamps, we'd do like this, right?
75
4 is 0, so that would actually give us a negative value at 0.
76
So here we go, and this is how we get this all set up.
77
Pretty straightforward to set this up.
78
I do mention though that with some controls, they give you the ability to set COV.
79
And you see the COV increment is set to 1 here, which is fine here.
80
But if we went to 0 to 5 volts and we were doing 0 to 5 inches for our actual pressure sensing,
81
maybe this was building static pressure, and we had 1 as our COV increment, that would not be good.
82
because change by one in pressure is significant.
83
So if this may be called COV increment, this may be called refresh rate, this may be called change rate, whatever.
84
Figure that out.
85
You want to do anywhere from like one to 5% of the actual throttle range or sensor span.
86
Sorry, not throttle range.
87
I started to get into, I've been thinking about PID loops lately.
88
So sensor span, your sensor span is the effective span of the sensor that is controlled.
89
So your sensor may actually have a broader range.
90
It may go to a negative value.
91
But your controlled range is just this 0 to 5.
92
Actually, I would argue it's like half to 2.5 is your controlled range.
93
But, you know, that's just semantics.
94
So you pick your controlled range.
95
In our case, we have 5, right?
96
So we would say, what is 1% of 5?
97
And it'd be 0, 5.
98
And so that's what we would refresh.
99
That would be our refresh rate.
100
These are all kind of really important things to know, and they're what trip up a lot of newer techs.
101
It's not terribly difficult.
102
On the output side, pretty much the same thing, right?
103
We have digital outputs, can configure those, can pick our data types.
104
we have our 0 to 10 volt outputs we can pick
105
that and it has a reverse action that's basically just like polarity
106
and then you know we can have 4 to 20 milliamp I didn't talk really about pulse
107
because I mean outside of monitoring metering and things like
108
that it's not something we use a whole bunch
109
so I hope this was helpful to you and I hope
110
that this really helped you start to figure out how to do inputs
111
and outputs and if you have any questions do Do not hesitate to go below the video and ask those.
112
Tomorrow we will start to look at how do you wire these things up.
113
Thanks a ton.
114
Take care.
同频道
FOR YOU
推荐视频
真实场景:工业控制系统的IO设置教学
这段视频展示了一位讲师在BAS Bootcamp中讲解如何设置输入输出(IO)的场景。就像你在工作中给同事讲解设备操作,或在课堂上听老师分析技术细节一样,这样的对话充满了专业术语和实用表达。对于想要提升英语口语的学习者来说,这类真实场景的内容能帮助你适应不同领域的交流方式,无论是应对雅思口语中的学术话题,还是日常工作中的技术讨论。
实用表达与搭配
- universal inputs:通用输入。在技术对话中,这类复合名词很常见,记住“universal”与“inputs”的搭配,能准确描述设备功能。
- digital input:数字输入。类似的还有“analog input”(模拟输入),是工业控制领域的核心术语,在讲解设备时经常用到。
- reverse action:反向动作。“reverse”与“action”的组合的表达,用于描述设备的操作模式,适用于技术说明场景。
- resistance tables:电阻表。“resistance”(电阻)和“tables”(表格)的搭配,在讨论温度传感器时必不可少。
- delta degrees Fahrenheit:华氏度差值。“delta”表示“差值”,这种表达在科学和工程领域中用来描述数值变化。
你的影子跟读挑战
现在就打开视频,找到讲师讲解“digital input”设置的部分(大约从“Let's take a look first at digital input”开始)。跟着讲师的节奏,逐句跟读,注意他的重音和停顿。比如,在说“when that's true in the program, it's going to represent a true or a one”时,“true”和“one”的强调要突出。完成3遍跟读後,用自己的话复述这段内容,录音并对比原音,检查发音和流畅度。这个方法就是“shadowspeak”,能有效提高英语发音和口语表达能力,特别适合英语口语练习和雅思口语练习。
视频中的语法
说话人最常用的结构,并附上视频中的原话:
| 结构 | 视频中的用法 |
|---|---|
| 被动语态 be + 过去分词 — 强调发生了什么,而不是谁做的 | are typically used · be called · are closed |
| 定语从句 who / which + 从句 — 补充说明人或事物 | input which is · case, which is · here, which is |
什么是跟读法?
跟读法 (Shadowing) 是一种有科学依据的语言学习技巧,最初开发用于专业口译员的培训,并由多语言者Alexander Arguelles博士普及。这个方法简单而强大:您在听英语母语原声的同时立即大声重复——就像是一个延迟1-2秒紧跟说话者的影子。与被动听力或语法练习不同,跟读法强迫您的大脑和口腔肌肉同时处理并模仿真实的讲话模式。研究表明它能显着提高发音准确性,语调,节奏,连读,听力理解和口语流利度——使其成为雅思口语备考和真实英语交流最有效的方法之一。