쉐도잉 연습: testing installation and what you need look for - 영상으로 영어 말하기 배우기

연습 모드 선택

각 모드는 전체 화면 연습실로 열립니다.

258 문장
문장이 너무 짧거나 길면 Edit를 눌러 조정하세요.
1
basic insulation
2
so what we've got is we've got the pit coming in here what we need to do is the first
3
we've got a few tests
4
that we need to go through the first one mostly
5
we do is doing the earthing system first we have our main earth we have our water pipe
6
which is our bonding conductor
7
they come back here to the earth bar all right we have our men link
8
which we're going to put in okay
9
now what we have is we have a main switch stove the stove's
10
now going to be an rcd okay this one's a circuit breaker
11
but we will be changing we have two rcds protecting power
12
and one protecting the light so our lighting circuit is the fan with the light switches here
13
then we have four power sockets two on each rcd then we have the stove down here with the appliance
14
and our earth point that's our first one here
15
so this is treated as a separate appliance okay so
16
when we're doing measuring today i want you to mega between the earth
17
and the earth point here to make sure it's got continuity first
18
and then what you do is you'll do an insulation test between here
19
and the earth pin or between here and the earth earth itself make sure
20
that the stove's turned on there's no use measuring something
21
if it's in turned in the on off position all elements have to be turned on okay
22
so that's our stove here we have a simple sweep fan
23
or exhaust fan this being the metal part of the frame
24
so we need to go from here to the earth pin
25
and then make sure that the fans turned on
26
and we do an insulation resistance test same as what i
27
was talking about here insulation resistance test to make sure it's not down the ground these have to be removed
28
when you're doing your circuit tests for the circuits
29
because this going to create a fault on itself so make sure it's unplugged and switches from the on position
30
so the first test we're going to do right is we're going to test the earthing conductor
31
we're going to use a thing called the mega sorry insulation resistance test it can't be called a mega
32
because it's a brand name so
33
when we have a look at this the blue scale is
34
what we're going to do in ohms the red scale is what we're going to do in insulation resistance test
35
you'll notice we have three
36
and five the first thing
37
i need to do is do a battery check battery check's important all right i'll make sure my button's released but
38
so what i do is shorten my meter leads together to a battery test okay
39
that's telling me the battery's okay it's in a good position
40
all right and then what i'll do is check my homage it's sitting on zero
41
so zoom in for ohms we've got zero
42
there sitting on zero perfect the other one then we do is we go to 500 volts
43
and it goes back nearly to 0 ohms on that side there.
44
All right.
45
So it reads two different ways.
46
Zero reads down here on the left.
47
Sorry, down towards this way and zero reads on the opposite side.
48
The difference with the red scale is that we're pumping 500 volts into 240 volt circuit, which is what this is.
49
If we were doing a three -phase circuit, we would do 1 ,000 volts.
50
Okay.
51
Remember, it's a DC.
52
This is DC, not AC that we're putting in we're putting dc in
53
so it has to be double the voltage okay
54
and dc will pick up faults a lot more than ac what's the problem with ac yeah
55
it's kind of moving up
56
and down it's going strong right dc is basically full strength all the time all right
57
it's going to put a charge or a
58
or a um demand on the circuits all the time it's not going to be moving up and down
59
all right look at the ac sine wave anyway the first thing we need to do
60
if you're checking under verification in the rule book it has all about visual faults
61
and then it starts like there's a little flow diagram
62
there the main thing you need to check is make sure the installation part
63
is that the main earth is working to the earth bar all right then we check the bonding conductors
64
and then we go through to check to all the what we call protective uh earths
65
which are the ones that run out with an active
66
and neutral to each power point
67
and then your body body conductor doesn't have an active
68
and neutral running out with it all right
69
so these are what we call protective earth which means is if we get a fault between active or neutral
70
the earth will give us a return path of current
71
so what i'm going to do what's my maximum resistance
72
so what i'm going to do is now select
73
it to um ohms three ohms all right the rule book says
74
it shouldn't be more than 0 .05 okay we don't want a high um resistance
75
because if we've got
76
that we've got a problem one thing
77
you need to be careful of is don't do it from here to the clip
78
so if i go from the earth bar i'm going to put my emmy
79
and link out as well
80
if you go from here on the earth bar don't do it to the um to the clip
81
because there could be a high resistance under the earth stake do you understand what i'm getting
82
it needs to go to the earth stake
83
which is sitting on top here all right
84
so i'm getting a resistance of um just over 1 .5
85
which is a fail it's more than 0 .5
86
so that's telling me it's a difference and
87
if i go here it's about the same sometimes you'd be surprised
88
when you go from the pipe to the clamp how much the resistance could change
89
all right because there could be a high resistance all right okay
90
so that tells me that fails that means to be adjusted
91
or looked at
92
if we have a strip earth the reason
93
i'm going to talk about the strip earth now is you won't have this tag on here
94
and you won't have the clamp a strip earth will come
95
out of the board run down straight in the ground
96
and that's it and that's about 25 mil square
97
so it's a very hard it's pretty hard to do a test
98
or a what we call um continuity test on a strip earth
99
because it's a set length
100
and it doesn't have any joins in it okay the reason we do this test is
101
because we've got this join here that can give us a high resistance all right
102
bonding clamps the same we have the same resistance so i'm going to go from between
103
the earth bar to my bonding clamp or my piece of water pipe
104
and the same thing it's over 1 .5 so it's failing all right
105
so at the moment i'm not having a good run
106
but as this board's a fault board it's got faults in it the water pipe
107
and the main earth are failed all right so we've done
108
that test the next test i do after
109
that is to check all my sub earths
110
so i'll go from the power point here that's telling me it's got two
111
and i work my way down to all my earths all right making sure
112
so these are not doing too well at the moment
113
because they're all very high readings this one hasn't even got it hasn't even moved
114
so that tells me that the earth's not even hooked up to
115
that one we come to here
116
this is reading down to one back of the batten holder
117
there's a little brass clip it sits in the back between the two pins
118
that's where i want you to test to make sure the earth there
119
so at the moment i'm testing between the main earth bar
120
and the back clip and there's nothing reading there so
121
that tells me that the earth is not um hooked up
122
so there's no earth continuity there all right get into my stove
123
and i've got continuity there a bit of a high resistance
124
but i'm still showing continuity
125
so now i've done all my earths all right done the checks
126
and done um what i need to check if they fail
127
or not but some of them are not even showing continuity
128
so the next thing i'm going to do is we're going to do the whole installation
129
we need to make sure that all circuit breakers are in the on position
130
the men is disconnected okay all right this um
131
the link has to be put through so my mains are going to be separated
132
but the problem is i've got to put a link over here
133
the reason i have to join this is why the meter is not connected exactly
134
so this is where my meter the reason the neutral small
135
on the meter is it's only going to read the voltage potential
136
it doesn't have current passing through the neutral will come from here to this link bar all right
137
when it goes from the link bar
138
it goes straight to the neutral bar the problem with the active active comes to here goes through the meter
139
and then back through the fuse back to
140
sorry the main switch um we don't have to disconnect
141
or do anything on the neutral bar here
142
but the active we have to put a short between so what we're going to do now is we're testing
143
between the actives right the neutral the neutral has been disconnected now
144
because we don't have it at the same potential as the earth
145
because the men has now been removed so the idea is to make sure
146
that the insulation resistance between the active
147
and neutral to earth is more than one mega ohm
148
so what i'm going to do now is we're going to put
149
that on to 500 volts
150
which we've got test me meter to make sure it reads down to zero
151
which it's doing okay now what we'll do
152
is i'll go from the top of the main switch to the earth bar now
153
that should be taking in my mains back to here
154
and it should be doing
155
so i've got between the active there now i'm going to test between the neutral as well between earth
156
and neutral so i've still got a high resistance
157
and the same with active to earth now see the active came down to a low value
158
now some people i tend to test the active and neutral separately
159
so that if there's a fault you can identify
160
but what some people will do is they will put a bridge between you
161
so if you want to do the whole insulation active
162
and neutral at the same time i'll put a bridge between active it's a slippery little shit
163
right so i've bridged the active and neutral together now watch
164
if i do that between earth and the neutral now i'll get a low reading
165
so now it's down to 0 .5 which is a fail okay
166
and that means it's failed so now what i do is
167
if i break that off and go between active i've got a fail down to zero point point.
168
five which is a file i need one mega minimum all right
169
so what another way
170
you can do as i see as a quick check is you can start turning off circuits
171
and if the meter creeps up that means you're eliminating the fault
172
so if i did that it only works more on rcds
173
because you're actually taking the active and neutral out of circuit
174
but we have identified that if i go between earth
175
and neutral it's actually all right it's reading a high resistance it's more than one mega ohm
176
so my fault is in the active conductor so
177
if i take out the lighting circuit it's now brought it up to one mega ohm
178
if i turned off the power circuit it didn't change it much
179
if i turn off the next one let's bring it let's brought it right up so it's removed it so
180
i seem to have a problem on the power circuit
181
and probably one of the lighting but
182
if i bring the lighting back in it actually brings it back to one mega ohm
183
but it could be a slight problem in there
184
when i did the second one and brought
185
that one back in it doesn't change much at all but
186
when i do the power it actually brings it back down all right
187
so the other one i can do the stove doesn't make any difference okay to change
188
this one it brings it up a little bit the power circuit
189
same with those i think me i would put my money back on the lighting circuit
190
so what we'll do now so if you do find a fault on the mains the next step you normally do
191
is you would go in and test each sub circuit.
192
Do you understand what I'm getting at?
193
So you turn all these off,
194
you'd go between earth and you start looking and turning on lever turned off and test between the active and neutral
195
and pick up each sub circuit.
196
So this one here is giving me more than one mega ohm.
197
That's okay.
198
I'll then test the next one, more than one mega ohm.
199
Come in here, test the active conductor and just below one mega ohm.
200
right so we've got a fault and we work our way along the circuits um
201
when we do insulation resistance test of a appliance what we will do is make sure
202
this is turned on into the
203
or on position the first thing i want to do is go back and check my earth
204
so what i'll do is i'll set it back to three atoms
205
make sure i've got continuity between here and my earth pin all right
206
so what's that telling me if i've got that there nothing's shorting between
207
what's that have i got an open circuit so there's no continuity
208
when i short the leads together they go back to zero all right so we'll just readjust that again sorry
209
but i'm getting no continuity
210
so this could be a built -in fault i've only picked a random board
211
so that's not quite going down
212
so i've got a high resistance on my earth there
213
so there's no real continuity of my earth
214
it should be going back to zero all right something simple all right the next thing
215
i'll do is go 500 volts test between earth
216
and what am i getting should be coming up back up
217
but i've got a high resistance there
218
so it means the insulation resistance is okay i'm also going to check to the earth pin as well
219
and i still have a high resistance so there's no short on
220
that at the moment the problem i've got i did identify is between the earth pin of the frame
221
and the earth sorry earth pin of the plug on the frame
222
there is a high resistance there all right it's down a bit but not not low enough
223
when we come to this one same one test between the frame
224
and the earth so what i'll do is i'll to three ohms okay
225
so now notice that one pretty much coming back to zero
226
that tells me my earth is all okay
227
and then what i'll do is i'll go back to 500 volts again
228
and we go between the earth pin and the active
229
and i have a very high high insulation value
230
there as well somewhere around about five meg everything you do on appliances
231
and the main installation has to be above one mega minimum all right
232
if it's less than one mega fails okay all right and what did we say between
233
single phase and three phase 500 volts on single phase a thousand
234
and four fifteen all right
235
so you're doing a three phase mater you've got to remember
236
it's going to be on a thousand volts all right
237
so as i said there's other tests the other test
238
we've got to do is check the continuity of the mains
239
so for me we leave this pushed into here
240
and check the polarity so i'm going to go between the main switch
241
and i'll go between here so i've got continuity on here
242
and then what i do is go between the neutral bar and there
243
so active is active neutral is neutral all right um rcd test
244
we also go through to make sure the actives are switching the active conductor
245
so what i'm going to do is we're going to pick
246
this one here it's turned off and make sure the active conductor
247
so that tells me that that's in the correct pole so
248
that first one there i'll do the second one the switch is turning on
249
and off so that identifies that the active is switching in the correct position all right
250
if i come down to this one
251
and pick up the active here i'm still doing it okay let's try the fourth one
252
all right so that tells me
253
that these two here are switching to this rcd okay these two here are switching to this rcd here
254
so they're all working correctly all right i want
255
you to go on the board here there's the list of all our tests
256
that we do are in the rule book there's five of them
257
or six sorry more tests as you work through them and
258
if you've got any problems give me a yell I'm going to go.

앱 다운로드

유창하게 말하는 데 필요한 모든 것

AI 발음 평가문장마다 점수 확인
IPA 발음 연습모든 소리 마스터
단어 학습나만의 단어장 만들기
단어 게임놀면서 외우기
FOR YOU

추천 영상

이 레슨의 어휘와 말하기 포인트

이 말하기 레슨은 영상 “testing installation and what you need look for”을(를) 바탕으로 합니다. 가장 자주 반복되는 단어는 다음과 같습니다: earth, test, active, neutral, resistance. 이 영상에는 섀도잉할 문장 258개와 단어 3039개가 있습니다. 말하는 구간의 길이는 15:49입니다. 화자는 분당 약 192단어로 빠르게 말하므로 연음과 약하게 발음되는 소리가 많습니다. 단어의 85%가 영어에서 가장 많이 쓰이는 3,000단어에 속합니다. 나머지는 연습 전에 미리 확인해 두세요.

이 영상의 핵심 어휘

영상에 나오는 익혀 둘 만한 단어 15개를 발음, 뜻과 함께 정리했습니다.

단어발음뜻
neutral 형용사/ˈnuː.tɹəl/중립의
conductor 명사/kənˈdʌktɚ/지휘자
metre 명사/ˈmiːtəɹ/미터, 메터
stove 명사/stoʊv/난로, 스토브
pipe 명사/ˈpaɪp/피리
hook 명사/hʊk/갈고리
stake 명사/steɪk/말뚝
voltage 명사/ˈvəʊltɪd͡ʒ/전압
element 명사/ˈɛləmənt/요소
select 동사/sɪˈlɛkt/고르다
connect 동사/kəˈnɛkt/잇다, 연결하다
pin 명사/pɪn/핀
pump 명사/pʌmp/펌프
pole 명사/pəʊl/극
slight 형용사/slaɪt/약간의

영상에 나오는 구동사

단어뜻
turn off 동사끄다, 턴오프하다
pick up 동사줍다
go back 동사돌아가다
come back 동사돌아오다
come up 동사올라오다
go down 동사내려가다
put through 동사바꿔주다

이 영상의 문법

화자가 가장 많이 쓰는 문형을 영상 속 실제 표현과 함께 정리했습니다.

문형영상 속 표현
수동태 be + 과거분사 — 누가 하는지보다 무슨 일이 일어나는지에 초점is treated · be turned · be removed
현재완료 have/has + 과거분사 — 과거의 일이 지금도 관련이 있을 때we've done · hasn't even moved · i've done
관계절 who / which + 절 — 사람이나 사물에 대한 추가 정보circuit, which is · earth which means · five which is

주의할 발음

화자는 I'm, I'll, we're 같은 축약형과 약화된 형태를 109번 사용합니다. 들리는 대로 짧게 발음하세요.

  • “sh”와 “zh” 소리: insulation /ˌɪnsəˈleɪʃən/, installation /ˌɪn.stəˈleɪ.ʃən/, verification /ˌvɛ.ɹə.fɪˈkeɪ.ʃən/, homage /(h)oʊˈmɑʒ/, shorten /ˈʃɔɹtn̩/
  • 긴 단어 — 강세 위치에 주의: continuity /ˌkɑn.tɪˈn(j)u.ə.ti/, insulation /ˌɪnsəˈleɪʃən/, installation /ˌɪn.stəˈleɪ.ʃən/, eliminate /ɪˈlɪm.ɪ.neɪt/, verification /ˌvɛ.ɹə.fɪˈkeɪ.ʃən/

한국어 화자가 어려워하는 소리:

  • /f/ — ㅍ(/p/)으로 바꾸지 말고 윗니를 아랫입술에 대기: fifteen /ˈfɪf.tiːn/, verification /ˌvɛ.ɹə.fɪˈkeɪ.ʃən/, fuse /fjuːz/
  • /v/ — ㅂ(/b/)과 구별하기: stove /stoʊv/, protective /pɹəˈtɛk.tɪv/, voltage /ˈvəʊltɪd͡ʒ/, verification /ˌvɛ.ɹə.fɪˈkeɪ.ʃən/, lever /ˈliː.və/
  • /z/ — ㅈ이 아니라 성대를 울리는 /s/: zoom /zuːm/, exhaust /ɪɡˈzɔst/, fuse /fjuːz/

이 영상으로 연습하는 방법

  1. 먼저 말하지 않고 영상을 끝까지 듣고 모르는 단어를 적어 둡니다.
  2. 0.75배속으로 한 문장씩 섀도잉을 시작하고, 익숙해지면 보통 속도로 돌아갑니다.
  3. 자신의 목소리를 녹음해 원본과 비교하고, neutral, conductor, metre 같은 단어에 특히 주의합니다.

쉐도잉이란? 영어 실력을 빠르게 키우는 과학적 방법

쉐도잉(Shadowing)은 원래 전문 통역사 훈련을 위해 개발된 언어 학습 기법으로, 다언어 학자인 Dr. Alexander Arguelles에 의해 대중화된 방법입니다. 핵심 원리는 간단하지만 매우 강력합니다: 원어민의 영어를 들으면서 1~2초의 짧은 지연으로 즉시 소리 내어 따라 말하는 것——마치 '그림자(shadow)'처럼 화자를 따라가는 것입니다. 문법 공부나 수동적인 청취와 달리, 쉐도잉은 뇌와 입 근육이 동시에 실시간으로 영어를 처리하고 재현하도록 훈련합니다. 연구에 따르면 이 방법은 발음 정확도, 억양, 리듬, 연음, 청취력, 말하기 유창성을 크게 향상시킵니다. IELTS 스피킹 준비와 자연스러운 영어 소통을 원하는 분들에게 특히 효과적입니다.

섀도잉 방법: 단계별 전체 가이드 읽기 →