So here we can see all of the liquid cooling infrastructure for the Grace Blackwell Rack.
2
Inside this Equinix data center in San Jose, California, there are hundreds of server racks,
3
some executing massive AI compute tasks for the company's renting space here to run thousands of graphics and sensor processing units.
4
There are eight GPU racks in here
5
and each rack has 72 GPUs inside of it
6
and all those chips get hot under heavy workloads server can boil your eggs
7
they are like raining at 80 degree celsius the chips themselves would melt down
8
if they weren't continuously cooled and keeping these chips cool requires a lot of water and power
9
which is a major reason why there's a national backlash against
10
ai data centers backlash against data centers is growing across the country.
11
71 % of respondents said they would oppose the construction of a data center in their local area.
12
Backlash is also growing around power, water costs, who pays, local and state leaders are hitting pause on new projects.
13
The rate payers, both electrical and water, have seen their rates be shot up.
14
They don't wanna have to pay for these data centers to be there.
15
The largest data centers can use up to five million gallons per day.
16
That's what a small town of up to 50 ,000 might use.
17
A few data centers are using that much water, but most communities in the U .S.
18
don't have the infrastructure to support that demand.
19
But not all data centers and ways of keeping them cool are created equal.
20
These servers are liquid -cooled in a closed -loop system, but liquid cooling is only the start of the water
21
and power equation because the facility still has to get rid of the heat that's been absorbed by the liquid.
22
How a data center does that is what really determines consumption rates.
23
This closed -loop system itself doesn't necessarily mean the data center doesn't use water.
24
How do we reject the heat from the closed -loop to the ambient environment?
25
That's where the water usage comes in.
26
From dry cooling to evaporative cooling towers and hybrid solutions in between, we visited data centers around the country and chip plants
27
that need even more water to find out how data centers really use water, what liquid cooling looks like,
28
and where the companies running the biggest AI workloads have room to improve.
29
Inside data centers with closed loop systems, hyperscalers often label their cooling systems as using zero water for a majority of the year.
30
What they're not taking into account is once that heat is moved off the chip, it has to get moved out of the building.
31
And that part takes water and power.
32
In fact, saving water often means using more power for cooling.
33
There's no sort of silver bullet, but at some point you need to eject that heat out to the atmosphere, and that's where those tradeoffs occur.
34
But inside the servers that zero water use is largely right.
35
Once a closed loop system is filled up, no more water is consumed in this part of the process, keeping those chips inside the servers cool.
36
This is one of the 18 compute trays.
37
the gpus sit underneath these copper cold plates
38
that have liquid running through them to remove the heat from the system
39
this is amd's helios the only real competitor to nvidia's industry leading racks vera rubin
40
and grace blackwell and both companies designed their latest systems
41
so they can be entirely liquid cooled this is a cooling distribution unit
42
that takes chilled water in from the facility filters it pumps it
43
and distributes it to all of the helios racks keeping them cool
44
we're doing about 750 gallons per minute of chilled water
45
but unlike some cooling systems this one is completely closed loop and so it's not a drain upon the resources
46
the biggest advantage of liquid cooling however comes from just how quickly it can bring chip temperatures down
47
so they can get back to work.
48
Water is about 3 ,000 times more effective than air at removing heat from the chips.
49
Therefore, you're able to increase the density in the same footprint.
50
There's giant gigawatt plus sites built to run AI workloads for single huge companies like SpaceX AI, OpenAI, Google, Meta, and Amazon.
51
Then there's co -location data centers like this one.
52
Equinix, a big beneficiary of the AI boom, provides the building, power, network connections, and cooling to companies renting space for their server racks like
53
these NVIDIA Blackwell racks owned by NVIDIA -backed AI software startup Alembic.
54
So we went to an Equinix data center where these servers
55
are running real workloads today to see how this looks when the systems are powered on.
56
So these white pipes that are coming in are coming from our facility.
57
So it's our chilled water infrastructure and then it goes across a heat exchanger plate.
58
So that's how we're able to maintain the temperature and flow of the stainless steel piping that's distributed to the
59
This Equinix data center in San Jose is on a closed -loop system, but it does still consume water.
60
Like many data center operators, Equinix doesn't disclose water consumption at individual sites like this.
61
In 2025, though, all Equinix operations consumed 1 .2 billion gallons of water, up 10 % from 2024.
62
We're in 77 metros
63
and you know our entire global water footprint is the equivalent
64
of about 16 18 -hole golf courses in the southwestern United States.
65
One of the leading suppliers of liquid cooling equipment to giants like NVIDIA and AMD is CoolIT.
66
All the cold plates, the heat exchangers, and the connecting tissue between them.
67
We've done that for 25 years.
68
COOL -IT was acquired by water treatment company Ecolab for $4 .75 billion in July,
69
as AI drives huge demand for an especially efficient system called direct -to -chip cooling.
70
Direct -to -chip cooling uses a coolant that includes glycol to help stop corrosion, freezing, or biological growth inside the highly sensitive systems,
71
but it's still primarily made of water.
72
Legacy data centers were often air -cooled, in which large, noisy fans push cool air through heat exchangers to carry the heat away.
73
Air -cooled is for, let's say, CPU -based servers, cloud servers, storage servers, networking equipment.
74
They only need air -cooled because their heat density is much lower than GPUs.
75
And for GPUs, due to the high power density, air -cooled system is not enough.
76
They run at such a high wattage, a high temperature.
77
You would need nearly hurricane -force winds to actually cool them down if you were just using air, which is why water is so effective.
78
Still, the sheer scale of this data center build -out has many residents worried.
79
More than 2 ,000 new data centers are planned in communities all across the country, on top of nearly 1 ,400 already in operation.
80
In many places, the water supply simply can't support up to 8 million daily
81
gallons needed at peak times for a 1 -gigawatt site like MEDA's in Lebanon, Indiana.
82
Because in reality, there's a big way water is still used, even when it's a closed -loop system.
83
That water has to get cooled back down using external cooling, a separate step from closed -loop systems inside the building.
84
And it turns out the less water you use for this, the more power you need.
85
So let's talk about the options.
86
The simplest approach is just use the outside air.
87
And it works pretty well in the wintertime when the air is cold.
88
Using ambient air is indeed the least water -intensive method.
89
Known as dry cooling, large fans blow air across heat exchangers, using that outside air to cool it down.
90
Those fans don't work so well when the outside temperature is high.
91
And that's when power -hungry cooling units, similar to household AC, need to kick on.
92
That's a very power -intensive process.
93
And that's exactly why we have power shortages in the summer, because everybody else turns on their AC.
94
Evaporative cooling is the most water -intensive method because water is lost in evaporation.
95
The hot water circulates through cooling towers or over wet pads that are exposed to air,
96
and the portion that evaporates carries the heat away with it.
97
In between those two extremes, hybrid methods are common as companies try to find a balance,
98
such as dry cooling in the colder months and evaporative cooling when it's hot outside,
99
or a fine mist of water is sprayed to cool the incoming air before it passes through the dry cooling system.
100
There are data centers in Texas and in Phoenix, you know, where's 100 degrees during the day.
101
They have the land to provide to the data centers, but they really are not the environment the data center should be in.
102
Companies often build water treatment plants to help treat and recycle the necessary water, like one promised by Elon Musk in Memphis
103
that's meant to turn treated municipal wastewater into cooling water for SpaceX AI's Colossus data centers.
104
While Colossus 1 came online rapidly back in 2024, construction on the water treatment plant has stalled.
105
Colossus is allocated up to 1 .28 million gallons of water per day, and reports indicate it uses an average of 800 ,000 gallons per day.
106
As more data centers turn to water -efficient cooling methods, more power is needed.
107
That's in addition to the power needed to run all the servers and equipment.
108
It's why new data centers will account for most of the projected increase in electricity demand over the next decade,
109
and why tech companies are building their own power plants, which also use a lot of water.
110
At the end of the day, cooling the massive projects needed to supply the AI boom currently requires either a large amount of water or power.
111
There are, however, companies working hard on ways to make it better.
112
One idea? make the chips themselves run less hot.
113
We provided over 25 degrees Celsius difference, or 40 degrees Celsius difference in the temperature, I mean, the thermal characteristics.
114
Lokwon Kim's South Korean chip startup, DeepX, makes a low -power AI processor that runs so cool, it doesn't even melt butter placed on top,
115
as shown in a demo filmed by DeepX.
116
We gave the same AI workload, and then we just put the butter on them.
117
Every chip melted each butter, except for the best chip.
118
Hyundai Motor Group Robotics Lab has announced that this year, their first commercialized robots will use our chips.
119
Lower heat chips are also in the works at SK Hynix, the world's leading maker of high bandwidth memory crucial for AI.
120
Its next generation iHBM is designed specifically to reduce heat generation, which would lower the water or power needed for cooling.
121
We developed IHBM with ICE technology.
122
ICE stands for integrated cooling element and we can reduce the thermal resistance by 30%.
123
At Cool IT, it's working on getting the liquid even closer to the chips.
124
There's some really cool instances of water almost in the chip or just on top of the chip.
125
That's all about being able to deliver even warmer water to the data center
126
and continuing this ride towards ever more efficient use of liquid cooling in data centers.
127
And at data centers like Equinix, efficient water use is crucial as AI workloads and business from customers continues to grow.
128
At Equinix, we take it very, very seriously.
129
Communities rightly have begun to ask the right questions.
130
Data centers consume energy, they consume resources like water, but they also provide a very critical function to modern society.

下載應用

流利口語所需的一切

AI 發音評分逐句打分
音標練習掌握每個音
詞彙學習建立你的詞庫
詞彙遊戲邊玩邊學

同頻道

FOR YOU

推薦影片

本課的詞彙與口語要點

這節口語課以影片“The Truth About How Data Centers Use Water And Power To Keep Cool”為素材。 影片中反覆出現的詞有:center, cooling, chip, heat, liquid。 這段影片共有 99 個句子、1919 個單詞可供跟讀。 講話部分時長為 11:44。 說話人語速自然,每分鐘約 163 個詞,接近日常對話。 只有 78% 的單詞屬於英語最常用的 3,000 詞,詞彙難度較高。

影片中的重點詞彙

影片中 15 個值得學習的單詞,附發音和釋義:

單詞發音釋義
chip 名詞/t͡ʃɪp/籌碼
server 名詞/ˈsɝvɚ/伺服器 /伺服器, 伺服器
liquid 名詞/ˈlɪk.wɪd/液體 /液體, 液態 /液態
loop 名詞/luːp/圈, 環 /環
rack 名詞/ɹæk/架子
gallon 名詞/ˈɡælən/加侖 /加侖
consume 動詞/kənˈsum/耗費 /耗費, 消耗
efficient 形容詞/ɪˈfɪʃənt/高效率
infrastructure 名詞/ˈɪnfɹəˌstɹʌkt͡ʃə/基礎設施 /基礎設施
butter 名詞/ˈbʌtɚ/牛油, bá-tah
density 名詞/ˈdɛn.sə.ti/密度
chill 動詞/tʃɪl/使變冷
melt 動詞/mɛlt/融化, 熔化
backlash 名詞/ˈbækˌlæʃ/反彈 /反彈
consumption 名詞/kənˈsʌmp.ʃən/消費 /消費

影片中出現的短語動詞

單詞釋義
fill up 動詞裝滿 /裝滿
find out 動詞找出, 查明
shoot up 動詞飆升 /飆升
turn out 動詞原來 /原來

影片中的語法

說話人最常用的結構,並附上影片中的原話:

結構影片中的用法
被動語態 be + 過去分詞 — 強調發生了什麼,而不是誰做的weren't continuously cooled · be shot · are created
現在完成時 have/has + 過去分詞 — 過去發生但與現在仍有關聯的事have seen · that's been absorbed · We've done

需要注意的發音

說話人用了 14 次縮略和弱讀形式,例如 doesn't, don't, we're。請按聽到的簡短形式來說。

  • “th” 音: thermal /ˈθɜːməl/, underneath /ˌʌndɚˈniθ/, bandwidth /ˈbændwɪdθ/
  • “sh” 和 “zh” 音: efficient /ɪˈfɪʃənt/, backlash /ˈbækˌlæʃ/, consumption /kənˈsʌmp.ʃən/, crucial /ˈkɹuː.ʃəl/, tissue /ˈtɪʃ.(j)u/
  • 長單詞——注意重音位置: infrastructure /ˈɪnfɹəˌstɹʌkt͡ʃə/, necessarily /ˌnɛs.əˈsɛɹ.ə.li/, primarily /ˈpɹaɪ.mə.ɹə.li/, electricity /ɪˌlɛkˈtɹɪsɪti/, electrical /ɪˈlɛktɹɪkəl/

中文母語者容易讀錯的音:

  • /v/ — 不要讀成 /w/,上齒輕觸下唇: server /ˈsɝvɚ/, intensive /ɪnˈtɛnsɪv/, sensitive /ˈsɛn.sɪt.ɪv/, vera /ˈvɪɹə/, evaporate /ɪˈvæp.ə.ɹeɪt/
  • 詞尾子音 — 要讀清楚,後面不要加母音: chip /t͡ʃɪp/, liquid /ˈlɪk.wɪd/, loop /luːp/, rack /ɹæk/, efficient /ɪˈfɪʃənt/
  • /r/ 和 /l/ 的區別: crucial /ˈkɹuː.ʃəl/, necessarily /ˌnɛs.əˈsɛɹ.ə.li/, primarily /ˈpɹaɪ.mə.ɹə.li/, electricity /ɪˌlɛkˈtɹɪsɪti/, electrical /ɪˈlɛktɹɪkəl/

如何用這段影片練習

  1. 先完整聽一遍影片,不要開口,記下不認識的單詞。
  2. 先用 0.75 倍速逐句跟讀,熟練之後再回到正常速度。
  3. 錄下自己的聲音並與原聲對比,特別注意 chip, server, liquid 這類單詞。

什麼是跟讀法?

跟讀法 (Shadowing) 是一種有科學依據的語言學習技巧,最初開發用於專業口譯員的培訓,並由多語言者Alexander Arguelles博士普及。這個方法簡單而強大:您在聽英語母語原聲的同時立即大聲重複——就像是一個延遲1-2秒緊跟說話者的影子。與被動聽力或語法練習不同,跟讀法強迫您的大腦和口腔肌肉同時處理並模模擬實的講話模式。研究表明它能顯著提高發音準確性,語調,節奏,連讀,聽力理解和口語流利度——使其成為雅思口語備考和真實英語交流最有效的方法之一。

影子跟讀法: 閱讀完整分步指南 →